Home>Products>Grid tie solar inverter>TLS10KTS-20KTS 2014 New Type

Appearance

 

Description

l   Applicationfor solar and wind system.

l   Strong IP65NEMA 4protection, completed sealed cover suitable for harsh environment.

l   Advanced MPPT tracking 

l   No isolation transformer H6 full-bridge structure, highest efficiency reach 97% (Europe 96.5%) 

l   Over voltage, short circuit, overload, overheat and islanding protection etc. 

l   Different national standards for choice through keypress.

l   Multi-language LCD display, convenient for users to monitor main parameters from different countries. 

l   Max MPPT votlage range

l   5 years warranty period can be extended to 25 years

Parameters

 

Model

TressSolar

10KTS

TressSolar

12KTS

TressSolar

12KTS

TressSolar

17KTS

TressSolar

20KTS

DC input

Max.DC Input Power

12000W

14000W

15500W

18000W

21000W

Max.DC Input Voltage

1000V

Max. DC Input Current

PV1(16A)

PV1(16A)

PV1(20A)

PV1(20A)

PV1(22A)

PF2(16A)

PF2(16A)

PF2(20A)

PF2(20A)

PF2(22A)

Number of independent MPPT 

inputs/strings per MPPT input

2/2

MPPT Voltage Range

300-800V

380-800V

380-800V

430-800V

430-800V

Power Off/On Voltage

70-100V

AC output

Power

10000W

12000W

15000W

17000W

20000W

Rated Voltage Range

3/N/PE,230/400Can be set according to different countries and regions requirement.

Frequency

Grid frequency 50Hz(60Hz)

Phase

3 Phase

Power Factor

0.9 Advance…0.9 Lag

Max. Current

16A

19.2A

24A

25A

27A

Current THD

At rated power and in the sine wave<3%

Efficiency

Max. Efficiency

97.80%

97.80%

98.80%

98.80%

98.80%

Euro Efficiency

97.40%

97.40%

97.80%

97.20%

97.20%

MPPT Efficiency

99.90%

 Protection Degree

IP65/NEMA 4X

 Cooling Method

Forced Air Cooling

 Noise

<50dB

 Data Interfaces

RS485 / RS 232/(standard),WiFi module/Ethernet/CAN(Optional)

 Isolation

Non Isolated

 Night Loss

<5W

 LED Display

3.5”,TFI-LCE

 Warranty

5 years

 The Grid Read Funciton

YES

 DC Switch

Integrate

Protection

Inverter

Input over voltage, output short circuit, overload ,overheat protection

Grid

Anti-islanding(IEEE 1547),over/under voltage of grid, over/under frequency of grid protection

Environment

Operation 

Temperature Range

Air Circulation-10℃~40℃, 50℃

Stored Temperature

-20℃~ 60℃

Relative Humidity

0~100%

Environment

Have no corrosion gas, flammable gas, oil mist,dust etc.

 